Procedure Detailed steps STE display
7 Set the heating maximum
airflow limit.
1.
Press the or buttons to set the maximum
limit for heating airflow. The setpoint will
change in 1 CFM increments.
2.
Press the
button to save the setpoint and
advance to the next function.
8 Set the minimum limit
for fan speed.
Not used for all models.
1.
Press the or buttons to set the minimum
limit for the fan speed. The setpoint will
change in 1% increments.
2.
Press the
button to save the setpoint and
advance to the next function.
9 Set the maximum limit
for fan speed.
Not used for all models.
1.
Press the or buttons to set the maximum
limit for the fan speed. The setpoint will
change in 1% increments.
2.
Press the
button to save the setpoint and
advance to the next function.
10 Set the dual duct
minimum airflow.
Not used for all models.
This setpoint is for the minimum airflow when a
dual-duct system is at temperature setpoint.
1.
Press the or buttons.
2.
Press the
button to save the setpoint and
advance to the next function.
11 Select a new
configuration function or
exit.
1.
Press the or buttons to select one of the
following:
STPT, BOX, ADVC, or RSTR options
BACK to choose another configuration
function EXIT.
2.
Press the
button to select the next function.
Procedure to set the airflow setpoints (continued)
Section 4: Configuring the controllers SimplyVAV
36 Revision E