Kmc-controls CEP-4703V Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Capteurs Kmc-controls CEP-4703V. KMC Controls CEP-4703V User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
CEP-4703/4703V 1 Installation Guide
3.437
[87.3]
1.568 [40]
2.6
[66]
[63.5]
2.5
2.5
[63.3]
3.28
[83.2]
2.6
[66]
CEP-4703
CEP-4703V
Removable conduit fitting
with 1/2" NPS threaded hole
Gear
disengagement
lever
Override input (remembers
position and closes valve on
no call
for heat or cool)
Cold water LAT sensor or
hot water setpoint resistor
Cold water setpoint
resistor or hot water
LAT sensor
Sensitivity
adjustment
Terminals
(under cover)
Installation Guide
Analog Electronic DAT Controller-Actuator
CEP-4703/4703V
CEP-4703 Mounting
CEP-4703 Mounting .........................................................................................1
CEP-4703V Valve Mounting .............................................................................2
Wiring Connections .........................................................................................3
Operation .........................................................................................................3
Troubleshooting ...............................................................................................4
No Rotation or Wrong Stroke Range ............................................................4
Wiring Issues ................................................................................................4
Maintenance ....................................................................................................4
Accessories ......................................................................................................4
More Information .............................................................................................4
Important Notices ............................................................................................4
NOTE: Thismountingsectionisspecic
to the CEP-4703. For mounting a
CEP-4703V, see CEP-4703V Valve
Mounting on page 2.
1. Ensure the damper or valve shaft can
move freely through its entire range
of motion, and x any binding before
installing the actuator. Turn the damper
blade to its fully closed position.
2. Press (to the right) and hold the gear
disengagement lever, rotate the actuator
to the fully closed position, and release
the lever.
NOTE: Depending on the damper-seal
design, backing the actuator o
its stop approximately 5° may
provide tight damper shut-o.
3. Align the actuator and slide it onto the
shaft.
4. Leaving a gap between the actuator
and mounting surface to prevent any
binding, nger-tighten the nuts on the
V-bolt.
5. Insert the non-rotation bracket (HMO-
4002 supplied or HMO-4001 “T” bracket
available separately) into the slot at the
base of the actuator (as shown in the
illustration).
6. Secure the non-rotation bracket with
two (2) #8 or #10 self-tapping screws.
7. Evenly tighten the V-bolt nuts 30 to 35
in-lb.
8. If desired, use a 7/64-inch hex key
wrench to loosen and position the end-
stop screw.
NOTE: The two holes at the top of the
actuator are NOT for use in
direct-coupled applications.
They are for remote mounting,
such as with the optional HLO-
4001 Crank Arm Kit (see the Data
Sheet).
Gear disengagement lever
Non-rotation bracket
(HMO-4002)
Mounting surface
Removeable conduit fitting
with 1/2" NPS threaded hole
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Installation Guide

CEP-4703/4703V 1 Installation Guide3.437[87.3]1.568 [40]2.6[66][63.5]2.5 2.5[63.3] 3.28[83.2] 2.6[66]CEP-4703CEP-4703VRemovable conduit fittingw

Page 2 - CEP-4703V Valve Mounting

CEP-4703/4703V 2 Installation GuideCEP-4703V Valve Mounting3.437[87.3]1.568 [40]2.6[66][63.5]2.5 2.5[63.3] 3.28[83.2] 2.6[66]CEP-4703CEP-4703VRe

Page 3 - Operation

CEP-4703/4703V 3 Installation GuideWiring Connections1. Loosen the screw on the conduit ing and lift up to remove the ing.2. Using a utili

Page 4 - Important Notices

CEP-4703/4703V 4 Installation GuideAccessoriesHCO-1151 Weather shield kitHLO-4001 Crank arm kitHMO-4001 Non-rotation “T” bracketHMO-4002 Rep

Modèles reliés CEP-4703

Commentaires sur ces manuels

Pas de commentaire